CRPS
CRPS 2U 1300W-2000W
Specifications
- Input Voltage: 90 - 264 Vac
- In Frenquency: 47 - 63 Hz
- Input Current: Max. 12A (110-127Vac); Max. 10A (200-240Vac)
- Hold-up Time: min. 12mS @ 50% load
- High Efficiency: 94%@50% Load
- MTBF : Min. 100,000 Hours @ 25 ℃
- Temperature: 0 ~ 50℃ Operating
- Altitude: 5000 meter(16,404 ft) Operating
- Relative Humidity: 20% - 90% RH Operating
- Dimension:
ERP2U: 75.6 x 83.4 x 250 mm (WxHxD),
Module: 73.5 x 40 x 185 (195) mm (WxHxD)
Features
- 80Plus Platinum Level
- Support PMBus 1.2
- High Efficiency 94%
- Internal Or’ing
Certification
- FCC/CE ; EN61000-3-2
- EN61000-4-2,3,4,5,6,8,11
- IEC/EN 60950-1; TUV/UL (CB)
- (Cetification without Power Cage)
Data Sheet
CRPS 2U 550W-800W
Specifications
- Input Voltage: 90 - 264 Vac
- In Frenquency: 47 - 63 Hz
- Input Current: 2.2A~6.9A (400W,550W), 10A-4A (800W)
- Hold-up Time: min. 12mS @ 50% load
- High Efficiency: 94%@50% Load
- MTBF : Min. 100,000 Hours @ 25 ℃
- Temperature: 0 ~ 50℃ Operating
- Altitude: "3049 m (10,000. ft for 400W-550W) operating
- 5000 meter(16,404 ft for 800W) Operating "
- Relative Humidity: 20% - 90% RH Operating
- Dimension:
ERP2U: 75.6 x 83.4 x 250 mm (WxHxD),
Module: 73.5 x 39 x 185 mm (WxHxD)
Features
- 80Plus Platinum Level
- Support PMBus 1.2
- High Efficiency 94%
- Internal Or’ing
Certification
- FCC/CE ; EN61000-3-2
- EN61000-4-2,3,4,5,6,8,11
- IEC/EN 60950-1; TUV/UL (CB)
- (Cetification without Power Cage)
Data Sheet
CRPS 1600W-2000W
Specifications
- Input Voltage: 90 - 264 Vac
- In Frenquency: 47 - 63 Hz
- Input Current: Max. 12A @ 110V-127 Vac; Max. 10A @ 200-240Vac; *10A @230-240Vac
- Output Power: 1000W @ 110-127Vac; 1600W/1800W/2000W @ 200-240Vac
- Hold-up Time: 12mS @ 70% Load
- High Efficiency: 94% @ 50% Load
- MTBF : 150,000 Hours @ 25 ℃
Temperature: 0 ~ 50℃ Operating - Altitude: 5000 meter(16,404 feet) Operating
- Relative Humidity: 20% - 90% RH Operating
- Dimension: 73.5 x 40 x 195 mm (WxHxD)
Features
- 80Plus Platinum Level
- Support PMBus 1.2
- High Efficiency 94%
- Internal Or’ing
Certification
- FCC/CE ; EN61000-3-2
- EN61000-4-2,3,4,5,6,8,11
- IEC/EN 60950-1; TUV/UL (CB)
Data Sheet
CRPS 1300W+
Specifications
- Input Voltage: 90 - 264 Vac
- In Frenquency: 47 - 63 Hz
- Input Current: Max. 12A @ 110V-127 Vac; Max. 7.5A @ 200-240Vac
- Output Power: 900W @ 110-127Vac; 1300W @ 200-240Vacr
- Hold-up Time: 12mS @ 70% Load
- High Efficiency: 94% @ 50% Load
- MTBF : 150,000 Hours @ 25 ℃
- Temperature: 0 ~ 50℃ Operating
- Altitude: 5000 meter(16,404 feet) Operating
- Relative Humidity: 20% - 90% RH Operating
- Dimension: 73.5 x 40 x 185 mm (WxHxD)
Features
- 80Plus Platinum Level
- Support PMBus 1.2
- High Efficiency 94%
- Internal Or’ing
Certification
- FCC/CE ; EN61000-3-2
- EN61000-4-2,3,4,5,6,8,11
- IEC/EN 60950-1; TUV/UL (CB)
Data Sheet